These are SC/APC connectors. "APC" stands for "Angled Physical Contact"; the connector end-face is polished at an 8-degree angle. This design provides lower return loss (typically 55dB or greater) compared to blue UPC connectors, offering better protection for optical signals. These are commonly used in PON (Passive Optical Network) systems.
This indicates the use of single-mode fiber (typically G.657A1 bend-insensitive fiber), which is suitable for long-distance transmission.
Multiple pigtails converge from the top into a single main cable, while at the bottom, they branch out into individual green SC connectors. This is the typical configuration for the output side of an optical splitter.
Operating Wavelength: 1260 ~ 1650 nm
Insertion Loss: ≤ 16.9 dB (based on a 1x32 configuration; loss increases with a higher number of split ports)
Return Loss: ≥ 55 dB
Operating Temperature: -40°C ~ 85°C
Fiber Type: G.657A1 Single-mode Fiber
FTTH (Fiber to the Home): Used in optical cross-connect cabinets or fiber distribution boxes to split an optical signal from the central office among multiple households.
PON (Passive Optical Network): Serves as a core optical splitting component in EPON or GPON networks.
Data Centers and LANs: Used for signal distribution within high-density fiber cabling systems.
Clean the end face: Before insertion, the end face of the SC/APC connector must be cleaned using a specialized cleaning tool to prevent dust from causing increased optical attenuation.
Avoid excessive bending: Although bend-insensitive optical fiber is used, a proper bend radius (typically no less than 10 mm) should still be maintained to prevent increased signal loss.
Ensure interface compatibility: Verify that the connected device also features an SC/APC interface. Connecting it to an SC/UPC (blue) interface by mistake will result in a significant increase in connection loss due to a mismatch between the end faces.